Bi-block system, floor mounted condensing unit, ceiling-mounted evaporator.
Electronic control panel with alarm module.
Expansion device: thermal expansion valve.
Terminal board inside the switchboard, pre-arranged for the connection to a door switch.
All compressors provided with crankcase heater.
Semi-hermetic compressors are protected by thermistors; models equipped with oil pump are further protected by a differential oil pressure switch.
Compressors with a displacement up to 52 m3/h are provided with direct start, those with higher capacity are equipped with part winding start.
All units are equipped with an adjustable low pressure switch as well as with an adjustable high pressure switch with automatic reset.
Panel provided with pressure switches, service valves and pressure gauges accessible also when the unit is in operation.
Sight glass and liquid line solenoid valve on all units.
All units are equipped with a liquid receiver with safety valve.
Suction accumulator.
Condenser fan pressure switch on all units. On request, condenser fan control by means of an electronic fan speed regulator.
Remote panel: already fitted with a 5 meters long connection cable (on request extension up to 20 meters). It consists only of the electronic control panel keyboard; the alarm display is placed on the condensing unit, near the switchboard.
Direct drainage of condensate.
Drain heater on all medium temperature, low temperature, multi-temperature and blast-freezing units. Guides for lifting forks in the lower part of the condensing unit's frame.
Pipe couplings are either unions or solder flanges.
The fan holding panels can be placed both on the front and on the cover of the unit (if necessary, it is possible to change the fan position also after the unit has been installed).
Standard evaporator fan cowl heater(s) on all blast freezing units.
Optionals:
Special voltage.
Water-cooled condenser: units equipped with water-cooled are also provided with a pressure controlled water valve controlling the condensation; low temperature units are also provided with a compressor cooling fan.
Voltage monitor.
Condenser fan speed regulator.
Switchboard heater.
Pressure gauges.
Snow protection: additional upper cover, additional support feet for raising the unit from the ground.